Between December, 1979, and July, 1980, 12 cases of legionnaires' disease were recognised in a district general hospital. 11 of the patients probably acquired their infection within the hospital. Epidemiological and environmental studies indicated that the plumbing system and possibly also the air-conditioning cooling-tower exhaust in the new building of the hospital were the sources of infection. Chlorination of the cold-water supply and raising the hot-water temperature appeared to terminate the outbreak.