Home LiteratureArticle Details
PMID: 2567304 Published · ppublish English Journal Article

Legionella spp. in a hospital hot water system: effect of control measures.

The Journal of hospital infection ·Vol. 13 ·No. 2 ·1989-02-00 ·Pages 121-31

Ezzeddine H, Van Ossel C, Delmée M, Wauters G

Abstract

Potential sources of Legionella spp. in a university hospital were investigated over 3 years in order to gain better understanding of the ecology and transmission of this organism to hospitalized patients. The survey highlighted the contamination of the hot water system with high concentrations of legionellas (up to 10(6) cfu 1(-1]. Legionella pneumophila serogroup 6 was predominant followed by L. pneumophila serogroup 10. Serogroup 1 and other species (L. longbeachae, L. micdadei) were rarely isolated. Serogroup 6 was also the predominant cause of nosocomial legionellosis in 15 sporadic cases in immunocompromised patients from 1981 to 1987. In light of this problem, several control measures were tried consecutively. A disinfection cycle with 6 ppm free chlorine failed to eradicate legionellas because of difficulties with the plumbing system. Raising the temperature in hot water tanks to 80 degrees C was effective locally, but mixer tanks where cold and hot water (60-65 degrees C) are mingled in order to achieve 45 degrees C became the principal reservoirs. Disconnecting the mixer tanks, maintaining a temperature of 60 degrees C in the heating tanks and accelerating the flow rate in the hot water system proved to be the most useful measures.

MeSH Terms
Belgium Cross Infection/prevention & control Hospital Bed Capacity, 500 and over Hot Temperature Humans Legionella/isolation & purification Legionellosis/prevention & control Maintenance and Engineering, Hospital/methods Sanitary Engineering Water Microbiology
Authors & Affiliations
4 authors, click to expand affiliations / ORCID
Ezzeddine H
Department of Microbiology, Cliniques Saint Luc, Brussels, Belgium.
Van Ossel C
Delmée M
Wauters G
Article Info
Journal
The Journal of hospital infection
Abbr.
J Hosp Infect
ISSN
0195-6701
Published
1989-02-00
Pages
121-31
Language
English
Region
England
NLM ID
8007166
Subset
IM
Analysis Services
Analysis Services

Contact

No. 2 Wenbo Road, Zhangqiu District, Jinan, Shandong

Qilu Normal University · Genelibs Bioinformatics Lab

750 Shunhua Rd, Jinan

2F, Bldg F, University Science Park

Tel: 0531-88819269

WeChat Official Account

Follow our WeChat subscription account for real-time updates and the latest in medical and biological research.


Business Email

E-mail: product@genelibs.com